Telecom site power
Tower Power Kits for solar-hybrid telecom sites
CRS PLUS supplies three standard 48V DC power configurations for base-station and tower sites in the Middle East: a rural single-sector site, a three-sector 4G/5G macro site, and a grid-connected urban site. Each kit combines the PV array, MPPT solar charge control, rectifier shelf, lithium battery, outdoor cabinet, distribution and site monitoring in a single order, with order-conformity inspection, documentation and delivery to port or site. Every kit is sized to the site's measured load, sun hours, grid availability and autonomy requirement before it is quoted.
Kit configurations
Reference configurations. Each kit is adjusted to the load, sun hours and autonomy requirement of the site, and the final configuration is confirmed on the quotation.
| Kit | Site class | Design load | PV array | Rectifier system | Battery | Generator |
|---|---|---|---|---|---|---|
| TPK-1 | Rural 1-sector 4G site, off-grid | 1.5 kW average, 2.2 kW peak | 3 kWp (6 × 550 W) | 200 A shelf, 2 × 3 kW (N+1) | 48V 200 Ah LiFePO4 (10 kWh) | 8 kVA class, auto-start on battery state of charge |
| TPK-3 | 3-sector 4G/5G macro site with microwave backhaul | 5 kW average, 7.5 kW peak | 10 kWp (18 × 550 W) | 400 A shelf, 4 × 3 kW (N+1) | 48V 400 Ah LiFePO4 (20 kWh), expandable to 900 Ah | 20 kVA class, auto-start on battery state of charge |
| TPK-G | Urban or peri-urban site with unreliable grid | 10 kW average, 14 kW peak | 6 kWp (11 × 550 W) | 400 A shelf, 4 × 3 kW, grid input with surge protection | 48V 200 Ah LiFePO4 (10 kWh), expandable | Optional; AC input for a portable generator |
TPK-1 · Rural 1-sector 4G site
Off-grid site with a small radio load. Solar and the lithium battery carry the site, and the generator recharges the battery when its state of charge falls, so it runs in short, efficient cycles rather than continuously. Typical use: rural coverage sites, greenfield sites without a shelter, and diesel-to-solar retrofits that keep the existing generator.
| Component | Reference specification |
|---|---|
| Design load | 1.5 kW average · 2.2 kW peak |
| PV array | 3 kWp · 6 × 550 W modules · pole or ground-mount racking rated for exposed sites |
| Solar charge control | 60 A MPPT, 48V, temperature-compensated charging |
| Rectifier system | 200 A outdoor shelf · 2 × 3 kW modules (N+1) · AC input for generator or grid |
| Battery | 48V 200 Ah LiFePO4 (10 kWh) · 100 Ah modules · BMS with RS485 / CAN |
| Distribution | DCDU with load breakers · 100 A AC input breaker · battery main breaker · anti-condensation heater |
| Enclosure | Outdoor integrated cabinet, IP55, fan-cooled, 3-point lock |
| Generator interface | Auto-start on battery state of charge (typically 40–50% start, 80–90% stop) · 8 kVA class |
| Monitoring | Site controller with SNMP over GPRS / 4G · door, temperature, smoke and mains-fail alarms |
TPK-3 · 3-sector 4G/5G site
Full macro site with three sectors and microwave backhaul. Solar supplies a large share of daytime energy, and the generator runs in a narrow, efficient band to recharge the battery instead of running continuously; the resulting reduction in generator hours depends on load, sun hours and battery size and is estimated in the offer. Typical use: macro sites, sites with 5G or multi-band radio upgrades, and towerco diesel-reduction programmes.
| Component | Reference specification |
|---|---|
| Design load | 5 kW average · 7.5 kW peak |
| PV array | 10 kWp · 18 × 550 W modules · ground-mount racking inside the compound |
| Solar charge control | 200 A MPPT, 48V, temperature-compensated charging |
| Rectifier system | 400 A outdoor shelf · 4 × 3 kW modules (N+1) · AC input for generator or grid |
| Battery | 48V 400 Ah LiFePO4 (20 kWh) · 100 Ah modules · BMS with RS485 / CAN · expandable to 900 Ah |
| Distribution | DCDU with load breakers · AC input breaker · battery main breaker · anti-condensation heater |
| Enclosure | Outdoor power cabinet plus separate outdoor battery cabinet, IP55, DC air-conditioned, 3-point lock |
| Generator interface | Auto-start on battery state of charge · 20 kVA class |
| Monitoring | Site controller with SNMP over GPRS / 4G · door, temperature, smoke, mains-fail and fuel alarms |
TPK-G · Urban solar + grid site
Grid-connected site with intermittent supply. Solar offsets daytime grid consumption and the battery carries the site through grid interruptions; battery capacity is sized to the outage profile, and a generator input is retained where outages are long or frequent. Typical use: urban and peri-urban sites, and programmes to reduce or remove standby generators.
| Component | Reference specification |
|---|---|
| Design load | 10 kW average · 14 kW peak |
| PV array | 6 kWp · 11 × 550 W modules · rooftop or shelter-mount racking |
| Solar charge control | 120 A MPPT, 48V |
| Rectifier system | 400 A outdoor shelf · 4 × 3 kW modules · AC grid input with surge protection |
| Battery | 48V 200 Ah LiFePO4 (10 kWh) · 100 Ah modules · BMS with RS485 / CAN · expanded to the outage profile |
| Distribution | DCDU with load breakers · AC input breaker · battery main breaker |
| Enclosure | Outdoor integrated cabinet, IP55, DC air-conditioned, 3-point lock |
| Generator interface | Optional · AC input available for a portable generator |
| Monitoring | Site controller with SNMP over Ethernet or 4G · door, temperature, smoke and mains-fail alarms |
Cabinets and modules supplied individually
Each kit component is also supplied on its own for retrofits, spares and capacity expansion.
| Item | Specification |
|---|---|
| Outdoor integrated power cabinet | 48V DC · 200 A or 400 A rectifier shelf · DCDU · breakers · heater · IP55 · fan-cooled or DC air-conditioned |
| Outdoor lithium battery cabinet | 48V LiFePO4 · 200 Ah to 900 Ah (up to 43 kWh) in 100 Ah modules · IP55 · 48V DC air conditioner · 3-point lock, hidden hinges, door alarm |
| Rectifier modules | 48V · 3 kW class · hot-swappable · including Huawei R4850-series and Vertiv R48-3000e3-series modules, matched to the shelf in service |
| Solar MPPT modules | 48V · 60 A to 200 A · shelf-mounted or standalone |
| PV modules and racking | 550 W to 650 W monocrystalline · pole, ground or rooftop racking rated for exposed sites |
| Site controller | SNMP · RS485 / CAN · GPRS / 4G or Ethernet · door, temperature, smoke and fuel inputs |
PV sizing by sun hours
Starting point for a 5 kW solar-hybrid site. Arrays for hybrid operation are sized at roughly 1.5 to 2 times the average site load; fully off-grid sites without a generator need a substantially larger array and battery.
| Region | Peak sun hours | PV for a 5 kW load |
|---|---|---|
| High irradiance (desert interiors, Arabian Peninsula interior) | 6+ | 8–9 kWp |
| Typical sunbelt sites | 5–6 | About 10 kWp |
| Moderate irradiance | 4–5 | 12–14 kWp |
| Low irradiance | Under 4.5 | Array +20–40%; wind hybrid assessed |
How a kit is sized
Each kit starts from the measured site load — average and peak — together with peak sun hours at the site, grid availability where there is a grid, the required battery autonomy and the generator already in place. The PV array, MPPT rating, rectifier capacity and battery are then sized together, so that the rectifiers can carry the load and recharge the battery at the same time when the generator or grid is running.
Two derating factors are built into every design: dust, which can reduce PV output by 15–25% over a dry season, and high ambient temperature, which lowers the safe lithium charge voltage and capacity. Both are reflected in the array size and the controller settings specified with the kit.
From specification to site
Site data: load, sun hours, grid uptime, autonomy and destination, in any format — a site list, load profile or tender specification.
Structured offer: kit configuration, lead time and warranty terms, typically within 72 hours.
Order conformity: inspection against the purchase order before shipment, with photographs and test records.
Compliance and freight: lithium battery dangerous-goods documentation, packaging and export clearance.
Delivery: DAP port or site, or EXW on request, with customs clearance arranged where required.
Documentation and supply terms
- Order conformity
- Each kit is inspected against the purchase order before shipment — component models, quantities, ratings and labelling — with photographs and test records supplied with the shipping documents.
- Lithium battery shipping
- LiFePO4 batteries ship as Class 9 dangerous goods with the UN 38.3 test summary and safety data sheet, packed and declared for sea or air freight as required.
- Delivery terms
- Quoted DAP port or site, or EXW on request. Customs clearance at destination is arranged where required; import permits and type approvals remain the buyer's responsibility and are stated on the quotation.
- Quotation
- Specifications on this page are reference configurations. The final configuration, lead time, warranty and delivery terms are stated on each quotation. Listing does not indicate stock held by CRS PLUS.
Questions
Frequently asked questions
Can a kit be adjusted to my site?
Yes. The three kits are reference configurations. Each is resized to the measured load, peak sun hours, grid availability and battery autonomy of the site before it is quoted, and individual components can be substituted to match equipment already in service.
How much PV does a telecom site need?
For solar-hybrid operation with a generator or grid, arrays are typically sized at 1.5 to 2 times the average site load — about 10 kWp for a 5 kW site with 5 to 6 peak sun hours. Sites with fewer sun hours need a larger array, and fully off-grid sites without a generator need substantially more PV and battery capacity.
Why lithium iron phosphate (LiFePO4) batteries?
LiFePO4 tolerates the deep daily cycling of a solar-hybrid site far better than lead-acid, keeps its capacity at higher temperatures, and its BMS reports state of charge over RS485 or CAN so the site controller can start and stop the generator on actual battery condition.
Can the kit use our existing generator and rectifier shelf?
Yes. The generator interface starts and stops an existing generator on battery state of charge, and where a Huawei or Vertiv rectifier shelf is already installed, matching 3 kW-class modules are supplied for it instead of a new shelf.
How are the lithium batteries shipped?
As Class 9 dangerous goods, with the UN 38.3 test summary and safety data sheet, packaged and declared for the chosen mode of transport. Delivery is quoted DAP port or site, or EXW on request.